Описание
Tungus 4 (MPR(N)-4-I-GE-U2) is a universal powder fire extinguishing module with a wide range of applications.
Modifications:
— MPP(N) -4(p) — I-GE-U2 and MPP (N)-4(n)-I-GE-U2 (ceiling and wall mounting) of normal design with a temperature range of operation from minus 50 to plus 50°C;
-MPP(N-T) -4(p) — I-GE-U2 and MPP(N-T) -4(n)-I-GE-U2 (ceiling and wall mounting) of special design with a temperature range of operation from minus 60 to plus 90°C;
— MPP(N-Vzr)-4(p)-I -GE-U2 and MPP(N-Vzr)-4 (n)-I-GE-U2 (ceiling and wall mounting) explosion-proof of normal design with a temperature range of operation from minus 50 to plus 50°C;
— MPP(N-Vzr-T) -4(p)-I-GE-U2 and MPP(N-Vzr-T) -4(n) — I-GE-U2 (ceiling and wall mounting) explosion-proof special design with a temperature range of operation from minus 60 to plus 90°C;
— MPP(N-C3)-4(p) — I-GE-U2 and MPP(H-C3) -4(H) — I-GE-U2 (ceiling and wall mounting) which includes MPP(H)-4(p) — I-GE-U2 or MPP(H) -4(h) — I-GE-U2 and USPAA -1 v5;
— MPP (N-RP)-4(p) — I-GE-U2 and MPP(N-RP)-4(n) — I-GE-U2 (ceiling and wall mounting) explosion-proof special design with a temperature range of operation from minus 50 to plus 50°C.
Brief technical specifications:
| Naming of the indicator | Meaning |
| Weight of fire-extinguishing powder, kg: | 4,0 |
| Overall dimensions, mm, no more than: | height — 195 diameter — 280 |
| Protected area, S: | class A — 40 sq.m class B — 16 sq.m |
| Protected volume, V: | class A — 100 cubic meters class B — 20 cubic meters |
| Tripping current, A, not less | 0,12 |
| Explosion protection marking: | 0ExiaIIВT3 X, RP ExiaI X |
* For detailed specifications of the module, see the data sheet
It is designed for automatic suppression of fire classes A (solid substances), B (liquid substances), C (gaseous substances), and E (electrical equipment that is under voltage without taking into account the breakdown voltage of the fire-extinguishing powder).