ГГПТ-7,0 Тунгус

  • Type:
    Gas fire extinguishing generators
  • Service life, years:
    10
  • Protected V cl. A to m3:
    7 m3
  • Protected V cl. In m3:
    7 m3

Описание

Tungus-7.0 Gas Fire Suppression Generator

Modifications:

— GGPT-7,0(p) TU 4854-021-54572789-12 – ceiling-mounted generator;
— GGPT-7,0(n) TU 4854-021-54572789-12 – wall-mounted generator

Brief technical specifications:

Naming of the indicator Meaning
Full weight of the GGPT, kg, no more than: 18,5
Overall dimensions, mm, no more than: height (with bracket installed)-315
length-340
width-302
Protected volume for extinguishing a sub-class A2, class B fire in a room with a leak parameter of 0.044 m-1, m3: 7,0
Release time of the gas extinguishing agent, s: 15…25
Tripping current, A, not less 0,85

* For detailed specifications of the module, see the data sheet

Appointment:

Distinctive features:
1) The GGPF is a compact, small-sized product that can be installed anywhere in the protected volume, regardless of its orientation in space.
2) The installation of the GGPF-7.0 does not require any major work, such as pipe wiring or complex valve systems for launching and supplying the gas fire extinguishing agent to the protected volume.
3) During operation at the facility, there is no pressure in the GGPT housing, so there is no need for constant monitoring of the gas fire extinguishing agent leakage in the generator housing, which is necessary in standard gas fire extinguishing systems. The GGPT itself is not subject to monitoring by the Rostekhnadzor services.
4) Due to the double purification, the gas fire extinguishing agent enters the protected volume with no mechanical impurities.
5) The GGPT is powered by a low-power electrical pulse (starting current of 0.12A).
6) The intended service life of the GGPT without special maintenance is 10 years.
7) When the GGPT is triggered, there is almost no recoil force, so no special measures are required during installation at the facility.
8) The possibility of using it as an autonomous fire extinguishing agent with widely used and inexpensive electronic launch units for autonomous fire extinguishing systems, such as the autonomous automatic signal-launching device USPA-1 ТУ 4371-032-00226827-99 and the signal-launching device USP-101 ТУ 4371-004-21326303-96.
9) The gas fire extinguishing agent does not have a negative impact on the performance of electronic equipment, which

  • Common
  • Protected volume, m3, class A/B: 7

Отзывы

Отзывов пока нет.

Будьте первым, кто оставил отзыв на “ГГПТ-7,0 Тунгус”

Ваш адрес email не будет опубликован. Обязательные поля помечены *